SA-P 6 kV 1.2 C HL2

Surge arresters OPN-P 6 kV 1.2 C UHL2 are designed to protect the insulation of electrical installations in 6 kV AC networks with a frequency of 50 Hz and isolated neutral from switching and lightning overvoltages. They are manufactured according to TU 27.12.10-057-21639232-2022 and comply with the requirements of GOST R 52725-2021.

Technical specifications:

  • Rated discharge current: 10 kA
  • Energy discharge class: 3
  • Safe failure current:
    • duration of at least 1 second — at least 0.6 kA
    • duration of at least 0.2 seconds — at least 40 kA
  • Impulse current 4/10 µs: 100 kA
  • Thermal energy, at least: 4 kJ/kV

These surge arresters provide reliable protection of electrical installations from overvoltages resulting from lightning strikes and switching operations.