SA-P 6 kV 1.2 C HL1

Surge arresters OPN-P 6 kV with a discharge capacity of 1.2 C are designed to protect the insulation of electrical installations in 6 kV AC networks with a frequency of 50 Hz and an isolated neutral from switching and lightning overvoltages. They are manufactured according to TU 27.12.10–041–21639232-2020 and comply with GOST R 52725-2021 requirements.

Technical specifications:

  • Rated discharge current: 10 kA
  • Explosion safety current:
    • duration of at least 1 second: at least 0.6 kA
    • duration of at least 0.2 seconds: at least 65 kA
  • Residual voltage at lightning impulse currents of 8/20 µs:
    • at 5 kA: 17.5 kV
    • at 10 kA: 19.2 kV
    • at 20 kA: 21.5 kV
  • Residual voltage at switching currents of 30/60 µs:
    • at 125 A: 14.2 kV
    • at 250 A: 14.7 kV
    • at 500 A: 15.4 kV
  • Residual voltage at a steep impulse current of 5 kA and duration of 1/10 µs: 20.9 kV
  • Classification voltage at 2 mA current: 7.5 kV
  • Thermal energy: at least 4.0 kJ/kV

These arresters provide reliable equipment protection, preventing damage caused by overvoltages, and contribute to the overall reliability of electrical networks.