SA-P 10 kV 0.8 C HL2
Overvoltage Limiters OPN-P 10 kV 0.8 C UHL2
Overvoltage limiters OPN-P 10 kV 0.8 C UHL2 are designed to protect the insulation of electrical installations in AC networks with a voltage of 10 kV, a frequency of 50 Hz, and an isolated neutral from switching and lightning overvoltages. The products comply with GOST R 52725-2021 and are manufactured according to TU 27.12.10-057-21639232-2022.
Technical Specifications:
- Nominal discharge current: 10 kA
- Discharge capacity class: 2
- Explosion safety current:
- duration of at least 1 second — at least 0.6 kA
- duration of at least 0.2 seconds — at least 20 kA
- Impulse current 4/10 µs: 100 kA
- Thermal charge: at least 1.1 C