SA-P 10 kV 0.8 C HL1

Overvoltage Limiters OPN-P 10 kV 0.8 C UHL1

Overvoltage limiters OPN-P 10 kV 0.8 C UHL1 are designed to protect the insulation of electrical installations in AC networks with a voltage of 10 kV, a frequency of 50 Hz, and an isolated neutral from switching and lightning overvoltages. The products comply with GOST R 52725-2021 and are manufactured according to TU 27.12.10–041–21639232-2020.

Technical Specifications:

  • Nominal discharge current: 10 kA
  • Explosion safety current:
    • duration of at least 1 second — at least 0.6 kA
    • duration of at least 0.2 seconds — at least 65 kA
  • Residual voltage during lightning current impulses with a duration of 8/20 µs:
    • at 5 kA — 31.5 kV
    • at 10 kA — 33.3 kV
    • at 20 kA — 36.8 kV
  • Residual voltage during switching currents with a duration of 30/60 µs:
    • at 125 A — 24.9 kV
    • at 250 A — 26.3 kV
    • at 500 A — 27.6 kV
  • Residual voltage during a steep current impulse of 5 kA with a duration of 1/10 µs: 39.4 kV
  • Charge capacity: 0.8 C
  • Impulse current 4/10 µs: 100 kA
  • Classification voltage at 2 mA current: 13.1 kV
  • Thermal charge: at least 1.1 C