Post Insulator IОS-110-400 M UHL1
The IОS-110-400 M UHL1 insulator is designed for insulating and securing live parts of electrical equipment in complete switchgear and outdoor switchgear (ORU) of power plants and substations with alternating voltage above 1000 V at frequencies up to 100 Hz. It is recommended for use in areas with harsh climatic conditions, including high atmospheric pollution, icing, and frequent fogs.
Technical Specifications:
- Rated voltage: 110 kV
- Creepage distance: 2050 mm
- Weight: 48.3 kg
- Minimum mechanical bending strength:
- Standardized according to GOST and factory TU: 4 kN
- Guaranteed by the manufacturer: 8 kN
- Actual test values: 10–13 kN
- Minimum torsional breaking moment:
- Standardized according to GOST: not standardized
- Standardized according to factory TU: 2.5 kN·m
- Guaranteed by the manufacturer: 4 kN·m
- Actual test values: 5–8.5 kN·m
- Lightning impulse withstand voltage: 450 kV
- One-minute power frequency withstand voltage in dry conditions: 230 kV
- Average wet power frequency flashover voltage:
- Standardized according to GOST and factory TU: ≥230 kV
- Actual test values: 302.3–307.7 kV
- Pollution degree in the area of application:
- Minimum standardized value according to GOST: I
- Actual test results: II
Advantages of IОS-110-400 M UHL1 «VOLTA» Insulators:
- High mechanical bending strength reserve.
- Confirmed torsion tests.
- Suitable for use in disconnectors.
- Pollution resistance, allowing operation in harsh conditions.
- High electrical performance, confirmed by tests.
- Low aging rate, ensuring high reliability over time.
- Easier installation and reduced metal consumption in structures due to reduced insulator weight.
Manufacturer's Warranty Obligations:
- Warranty period: 10 years from the date of commissioning.
- Total service life: at least 35 years.
Transportation Preservation Measures:
Each insulator is packed in a wooden crate and individual polymer packaging, protecting it from contamination and ensuring delivery in a clean condition to the installation site.