LK 120/150-ID
Polymer suspension line insulators type LK 120/150-ID are designed for securing and insulating conductors of overhead transmission lines (OL) and switchgear (SG) of power plants and substations for alternating current with a voltage of 150 kV and a frequency up to 100 Hz. They ensure reliable operation at ambient temperatures ranging from -60 °C to +50 °C. The climatic version and placement category correspond to UHL 1 according to GOST 15150. The insulators are manufactured according to TU 3494-016-82442590-2011 and comply with standards GOST 28856, GOST R 55189, and IEC 61109.
Technical Specifications:
- Rated voltage: 150 kV
- Specified mechanical load: 120 kN
- Overall height (H):
- LK 120/150-ID-2-SP: not more than 1580 mm
- LK 120/150-ID-3-SP: not more than 1700 mm
- LK 120/150-ID-4-SP: not more than 1820 mm
- Insulation height (L):
- LK 120/150-ID-2-SP: at least 1370 mm
- LK 120/150-ID-3-SP: at least 1490 mm
- LK 120/150-ID-4-SP: at least 1610 mm
- Creepage distance:
- LK 120/150-ID-2-SP: at least 3460 mm
- LK 120/150-ID-3-SP: at least 4235 mm
- LK 120/150-ID-4-SP: at least 5350 mm
- Withstand voltage:
- Full lightning impulse:
- LK 120/150-ID-2-SP: 750 kV
- LK 120/150-ID-3-SP: 775 kV
- Full lightning impulse: