The wedge-type tension clamps of types NK-120, NK-160, and NK-210
The wedge-type tension clamps of types NK-120, NK-160, and NK-210 are designed for securing non-insulated conductors to insulating suspensions of anchor, anchor-angle, and terminal supports. The strength of the conductor fixation in the clamp is 95% of the conductor's breaking force. Manufactured according to TU 3449-001-52819896-2010.
Technical Specifications
- NK-120/21.6-22.4: intended for conductors of brands AC240/32, AC240/39, AC240/56. Breaking load — not less than 120 kN. Weight — not more than 9.0 kg.
- NK-160/23.8-25.2: compatible with conductors AC300/39, AC300/48, AC300/66, AC300/67, AC315/21.8, AC315/51.3, AC330/30, AC330/43. Breaking load — not less than 160 kN. Weight — not more than 10.0 kg.
- NK-160/26.6-27.7: suitable for conductors AC400/27.7, AC400/51.9, AC400/18, AC400/22, AC400/51, AC400/64. Breaking load — not less than 160 kN. Weight — not more than 10.0 kg.
- NK-210/28.8-30.6: intended for conductors AC450/56, AC500/26, AC500/34.5, AC500/64, AC400/93. Breaking load — not less than 210 kN. Weight — not more than 11.3 kg.