SA-P 330 kV 2.0 C

Overvoltage Limiter OPN-P 330 kV 2.0 C

The nonlinear overvoltage limiter (OPN) is designed to protect the insulation of electrical installations in AC networks with a voltage of 330 kV, a frequency of 50 Hz, and an effectively grounded neutral from switching and lightning overvoltages. The product complies with GOST R 52725-2021 and is manufactured according to TU 27.12.10-058-21639232-2022.

Technical Specifications:

  • Nominal discharge current: 10 kA
  • Explosion safety current:
    • duration of at least 1 second — at least 0.6 kA
    • duration of at least 0.2 seconds — at least 65 kA
  • Impulse current 4/10 µs: 100 kA
  • Climatic design and placement category according to GOST 15150: UHL1
  • External insulation design: for areas with pollution degree III

Residual Voltage Parameters:

  • During lightning current impulses with a duration of 8/20 µs:
    • at 5 kA — 612.0 kV
    • at 10 kA — 672.0 kV
    • at 20 kA — 739.0 kV
  • During switching currents with a duration of 30/60 µs:
    • at 250 A — 504.0 kV
    • at 500 A — 517.0 kV
    • at 1000 A — 539.0 kV
  • During a steep current impulse of 10 kA with a duration of 1/10 µs: 726.0 kV

Additional Characteristics:

  • Charge capacity: 2.0 C
  • Capacity class: 4
  • Classification voltage at 2 mA current: 275.0 kV
  • Thermal energy: at least 7.0 kJ/kV
  • Active power loss: at least 4.5 kJ
  • Creepage distance: 960 cm