SA 20 kV 0.6 C HL1

Overvoltage Limiters OPN 20 kV 0.6 C UHL1

Overvoltage limiters (OPN) are designed to protect the insulation of electrical installations in AC networks with a voltage of 20 kV, a frequency of 50 Hz, and an isolated neutral from switching and lightning overvoltages. The products comply with GOST R 52725-2021 and are manufactured according to TU 27.12.10–039–21639232-2020.

Technical Specifications:

  • Nominal discharge current: 5 kA
  • Explosion safety current:
    • duration of at least 1 second — at least 0.6 kA
    • duration of at least 0.2 seconds — at least 40 kA
  • Residual voltage during lightning current impulses with a duration of 8/20 µs:
    • at 2.5 kA — 53.5 kV
    • at 5 kA — 57.6 kV
    • at 10 kA — 64.1 kV
  • Residual voltage during switching currents with a duration of 30/60 µs:
    • at 125 A — 56.5 kV
    • at 250 A — 59.6 kV
    • at 500 A — 62.7 kV
  • Residual voltage during a steep current impulse of 5 kA with a duration of 1/10 µs: 60.3 kV
  • Charge capacity: 0.6 C
  • Impulse current 4/10 µs: 65 kA
  • Classification voltage at 1 mA current: 24 kV
  • Thermal charge: at least 1.1 C