SA 15 kV 1.2 C HL1

Overvoltage Limiters OPN 15 kV 1.4 C UHL1

Overvoltage limiters (OPN) are designed to protect the insulation of electrical installations in AC networks with a voltage of 15 kV, a frequency of 50 Hz, and an isolated neutral from switching and lightning overvoltages. The products comply with GOST R 52725-2021 and are manufactured according to TU 27.12.10–041–21639232-2020.

Technical Specifications:

  • Nominal discharge current: 10 kA
  • Explosion safety current:
    • duration of at least 1 second — at least 0.6 kA
    • duration of at least 0.2 seconds — at least 65 kA
  • Residual voltage during lightning current impulses with a duration of 8/20 µs:
    • at 5 kA — 51.2 kV
    • at 10 kA — 56.0 kV
    • at 20 kA — 62.8 kV
  • Residual voltage during switching currents with a duration of 30/60 µs:
    • at 250 A — 41.4 kV
    • at 500 A — 42.8 kV
    • at 1000 A — 45.0 kV
  • Residual voltage during a steep current impulse of 10 kA with a duration of 1/10 µs: 61.0 kV
  • Charge capacity: 1.4 C
  • Impulse current 4/10 µs: 100 kA
  • Classification voltage at 2 mA current: 22.0 kV
  • Thermal energy: at least 4.0 kJ/kV