Bushing insulators

IPK-10

Polymer bushing insulators of the IPK-10 series are designed for conducting and connecting current-carrying elements in electrical apparatuses and distribution devices of power stations and substations operating with alternating current at a voltage of 10 kV and a frequency of up to 100 Hz. They ensure reliable performance within an ambient temperature range from -60 °C to +50 °C. The climatic version is UHL, and the placement category is 1 according to GOST 15150.

Key Technical Specifications:

  • Rated Voltage: 10 kV
  • Creepage Distance of External/Internal Part of Insulator: 440 mm / 255 mm
  • Withstand Voltage of Full Lightning Impulse: 80 kV
  • Withstand Voltage at 50 Hz in Dry Conditions: 45 kV
  • Withstand Voltage at 50 Hz under Rain: 30 kV
  • Breakdown Voltage in Insulating Medium (at least): 80 kV
  • Permissible Pollution Degree According to GOST 9920: IV

Modifications of IPK-10 Insulators:

  1. IPK-10/630-IV/II-A UHL1
    • Bus Material: Aluminum
    • Rated Current: 630 A
    • Minimum Breaking Bending Strength: 8 kN
    • Creepage Distance of Insulator Sides: 420 mm / 300 mm
    • Weight: 5.7 kg
  2. IPK-10/630-IV/II-AM UHL1
    • Bus Material: Coated Copper
    • Rated Current: 630 A
    • Minimum Breaking Bending Strength: 8 kN
    • Creepage Distance of Insulator Sides: 420 mm / 300 mm
    • Weight: 6.8 kg
  3. IPK-10/1000-IV/II-A UHL1
    • Bus Material: Aluminum
    • Rated Current: 1000 A
    • Minimum Breaking Bending Strength: 8 kN
    • Creepage Distance of Insulator Sides: 420 mm / 300 mm
    • Weight: 5.7 kg
  4. IPK-10/1000-IV/II-AM UHL1
    • Bus Material: Coated Copper
    • Rated Current: 1000 A
    • Minimum Breaking Bending Strength: 8 kN
    • Creepage Distance of Insulator Sides: 420 mm / 300 mm
    • Weight: 7.8 kg